Innovative plug-in system for plugging in and out of branch breakers, with higher user-friendly aspects
Innovative plug-in system Many ideas for the highest safety: double door construction, busbar support, protection cover, etc. Passed the strict in-house test. |
Plug-in system
Model |
Wiring system |
Main [A] |
Branch [mm] |
Branch space [Pole] |
W [mm] |
H [mm] |
D [mm] |
---|---|---|---|---|---|---|---|
GPDS254-12 |
3φ4W |
250 |
108 |
12 |
500 |
1000 |
200 |
GPDS254-24 |
3φ4W |
250 |
216 |
24 |
500 |
1100 |
200 |
GPDS254-36 |
3φ4W |
250 |
324 |
36 |
500 |
1200 |
200 |
GPDS254-48 |
3φ4W |
250 |
432 |
48 |
500 |
1300 |
200 |
GPDS254-60 |
3φ4W |
250 |
540 |
60 |
500 |
1400 |
200 |
GPDS254-72 |
3φ4W |
250 |
648 |
72 |
500 |
1500 |
200 |
GPDS254-84 |
3φ4W |
250 |
756 |
84 |
500 |
1600 |
200 |
Note: Be sure to unload the breaker when plugging in and out.
Plug-in unit
Model |
Installable Pole |
Unit Height [mm] |
Branch space [mm] |
---|---|---|---|
GPUS254-12 |
12 |
450 |
108 |
GPUS254-24 |
24 |
550 |
216 |
GPUS254-36 |
36 |
650 |
324 |
GPUS254-48 |
48 |
775 |
432 |
GPUS254-60 |
60 |
875 |
540 |
GPUS254-72 |
72 |
975 |
648 |
GPUS254-84 |
84 |
1075 |
756 |
Plug-in branch unit
Reference standard |
IEC61439-1, 2 |
|
---|---|---|
Wiring system | 3-phase, 4-wire | |
Rated Frequency |
50Hz |
|
Rated Insulation Voltage (Ui) |
650V |
|
Rated Operational Voltage (Ue) |
415V |
|
Rated Current |
250A |
|
|
415V |
200V |
Rated conditional short-circuit current (Icc)* |
36kA |
50kA |
Rated short-time withstand current (Icw)* | 18kA 0.2s | 18kA 0.2s |